Skip to content
SunGeneAgricultural IoT
← Back to product
SunGene
Agricultural IoT
Product Family Selection Sheet
SG-EM-219: Three-Phase Direct-Connected AMI Smart Meter

Three-Phase Direct-Connected Smart Energy Meter

Direct-connected three-phase four-wire energy meter for circuits up to 100 A, with an RS485 hardware option for compatible remote-reading systems.

Category: Energy & Utility Metering

Pictured: SG-EM-219 — Three-Phase Direct-Connected AMI Smart Meter.

Specifications & version options

ConnectionThree-phase four-wire, direct-connected
Nominal voltage220 / 230 / 240 VAC phase-voltage references; 0.6–1.3 Un operating range
Frequency50 Hz ±5%
Current0.25–5(100) A; starting current 0.4% Ib
Energy accuracyActive Class 1; reactive Class 2
Pulse constants1000 imp/kWh and 1000 imp/kvarh
CommunicationRS485 available; infrared, PLC, RF and cellular options are configuration-dependent
Power consumption≤2 W; 10 VA
Environment-25 to 70 °C operating; -40 to 70 °C storage; ≤95% RH; IP54
DisplayLCD
Dimensions / weight300 × 172 × 85.5 mm; approximately 1.8 kg

Confirm the wiring and communication configuration

This meter connects directly to the circuit. Communication modules and protocols are selected for each order.

  • Use this selection for three-phase four-wire direct connection up to 100 A; use a CT-operated meter for higher-current circuits.
  • The current range is 0.25–5(100) A, with active-energy Class 1 and reactive-energy Class 2.
  • The nominal phase-voltage references are 220 / 230 / 240 VAC, with an operating range of 0.6–1.3 Un; confirm the destination wiring standard before quotation.
  • For RS485 remote reading, match the selected meter's protocol and data profile to the receiving system before commissioning.
  • Infrared, PLC, RF and cellular paths are configuration-dependent options, not standard simultaneous interfaces.
  • The enclosure is IP54, measures 300 × 172 × 85.5 mm and weighs approximately 1.8 kg. Certificates and regional approvals are checked for the ordered configuration.

Typical applications

  • Farm pump-room and greenhouse sub-metering on direct-connected three-phase circuits
  • Remote meter reading through a confirmed RS485 or optional communication module
  • Operational energy monitoring for farm panels, equipment groups and distributed sites
  • Import / export and multi-rate metering only when the quoted configuration includes those functions

Inquiries: contact@sungeneiot.com · sungeneiot.com

Select the required measurements and connection options from this sheet. Include the quantity, destination and accessories in your equipment request.