Equipment selection guide
Temperature Monitoring Gateways for Greenhouses & Produce
Connect greenhouse or produce-room temperature instruments. Compare wired and wireless inputs, record accuracy and timestamps, and plan alarm delivery.
Product-family illustrations
Compare individual equipment specifications ↓1. Purpose
Bring greenhouse or produce-room temperature readings into the records your team uses.
2. Suitable sites
Greenhouse growing zones, produce cold rooms and farm temperature instruments.
3. What to send
Send the country, measurement locations, existing display or sensor model, power and receiving application.
Connect a greenhouse or produce-room temperature point
Send the measurement location, range, point count and existing instrument details. Include power, network and where the readings or alarms should appear.
When to use this guide
Reuse a documented temperature output or add the right sensor and input for the greenhouse or produce room. Match the measurement and connection separately.
Individual equipment specifications
Connect an existing produce-room temperature display
A produce cold room has a working temperature display. The farm team needs readings in the office and a record of temperature excursions. Use the display’s documented output to select the receiving input and gateway.
For an existing Modbus temperature instrument, a compatible RS485 gateway can poll the documented temperature value and forward it through Ethernet or 4G to the agreed system. Check the register, units, scaling and update time before choosing the gateway. A bare resistance probe or thermocouple needs a matching input or transmitter; it cannot be connected to an RS485 terminal as if it were a digital instrument.
- Probe / instrument
- Matching input
- Gateway + uplink
- Temperature record
Compare the connection and the test
- Modbus temperature display
- Connection to consider: RS485 Modbus RTU polling
- Document or test needed: Register address, data type, units and scaling
- 4-20 mA transmitter
- Connection to consider: Compatible analog input
- Document or test needed: Loop wiring, supply and measurement endpoints
- RTD or thermocouple probe
- Connection to consider: Matching temperature input / transmitter
- Document or test needed: Probe type, wiring and complete measurement accuracy
- Wireless room sensor
- Connection to consider: Matching gateway and network
- Document or test needed: Regional radio plan, room coverage and reporting interval
Before choosing hardware: four connection checks
Compare the options
Select the temperature sensor before the gateway
Choose the sensor for the greenhouse, produce room or measurement point, including range, accuracy and placement. Match a room sensor, remote probe or existing instrument to its receiving input and the required data connection.

- 01
Sensor / probe
- 02
Compatible interface
- 03
Gateway + backhaul
- 04
Trends + alarm rules
Room / cabinet air
Monitor ambient conditions at a representative location.
Check before selection
Temperature range, humidity, response time and placement away from local heat sources. Enclosure and probe choice affect response.
Remote / process probe
Measure at a point separated from the electronics, subject to probe suitability.
Check before selection
Probe type, input support, immersion/mounting method, cable and calibration requirements. A room sensor is not automatically suitable for a process.
Existing transmitter
Reuse supported RS485/Modbus or analog temperature signals.
Check before selection
Register/scaling or analog input compatibility, sample interval, timestamps and offline buffering. Confirm alarm operation on the agreed platform.
Check the selected model
Specify the selected sensor range, accuracy, calibration and installation procedure for the measurement. Include the required records and acceptance criteria for produce storage or another regulated measurement.

Connecting field equipment
Illustration: farm workbench with field instruments, cables, power accessories and an equipment enclosure.
Connect the greenhouse or produce-room measurement
The sensor or instrument measures temperature. A matching input reads its output, and the chosen gateway delivers the agreed fields to the receiving application. Keep the growing zone or room identity, units and original observation time with the reading.
Choose the sensor and receiver together
Use documented RS485 instruments, LoRaWAN temperature nodes, probe transmitters or suitable temperature-input modules. Include air, liquid or surface measurement, range, accuracy, supply and mounting. For wireless points, plan coverage, regional settings and the reporting interval.
Assign the alarm and the response
Set high/low thresholds, persistence, reset behavior and missing-data notifications with the greenhouse or produce-room operator. Record the location and the person responsible for responding. Include the receiving application and any local alarm requirement in the project scope.
Check accuracy and missing readings separately
Set alarms for the room’s operating pattern
Selection worksheet
Choose the temperature data path
Existing RS485 instruments
- Hardware path to review
- Compatible Modbus RTU input → gateway → agreed MQTT or SCADA endpoint
- Confirm before quotation
- Protocol, register map, sensor power and selected firmware; RS485 alone is not a compatibility guarantee.
Distributed wireless temperature points
- Hardware path to review
- Temperature node → LoRaWAN gateway → network server → customer application
- Confirm before quotation
- Regional radio plan, indoor coverage, sensor accuracy and reporting interval.
Remote site with cellular coverage
- Hardware path to review
- Temperature sensor → compatible 4G RTU / gateway → customer cloud
- Confirm before quotation
- Country bands, SIM, peak power, data format and upstream authentication.
Show the remaining worksheet rows
Key points
- Reuse a compatible temperature instrument
- Compare wired RS485 and wireless LoRaWAN sensors
- Select Ethernet or a suitable cellular uplink
- Agree temperature thresholds and missing-data notifications
Technologies
- Temperature monitoring
- Humidity
- LoRaWAN
- RS485
- NB-IoT
- 4G LTE
- MQTT
- Modbus TCP
Related pages
Official technical references
Protocol specifications for the connections described in this guide.
FAQ
What does a farm temperature monitoring gateway do?
It connects the documented sensor or instrument output to the agreed receiving application. Select the input, protocol and delivered fields for that arrangement; include the measurement identity, units and original timestamp.
How do I choose a wired or wireless connection?
Start with the sensor output, distance, available power, reporting interval and receiving system. Use a compatible wired input for existing instruments. For wireless points, include the local radio plan, receiver and coverage at the growing zone or produce room.
What information is needed before quotation?
Tell us the country and what needs temperature monitoring. A photo or existing sensor model helps if available. We then confirm range, accuracy, number of points, power, communications and the alarm destination before quotation.
How does the temperature hardware connect to an existing platform?
Specify the receiving application and its required interface, fields, authentication and timestamps. The equipment list identifies the sensor, receiving input, gateway and any separate protocol conversion or integration work.
Will temperature alarms still arrive during a network outage?
Remote notification needs a working communication path. Include local alarms, backup power and the receiving system’s missing-data threshold in the plan. For recorded data, use the selected device’s storage specification and test reconnection and restart with the original measurement timestamps.
Can I connect a PT100 directly to an RS485 gateway?
Only if the gateway includes a documented PT100-compatible measurement input. An RS485 communication port alone cannot measure a resistance probe. Otherwise use a suitable temperature input module or transmitter.
Why does the gateway show a temperature ten times the display value?
Check the instrument register map for scaling, units and data format. A successful protocol response can still be decoded incorrectly. Compare the mapped reading with the display before changing alarm thresholds.
Should a disconnected temperature sensor show zero?
Show a missing or invalid measurement separately from a measured zero. Test the instrument fault indication and the receiving system’s stale-data handling during commissioning.
Get selection help
Tell us what you want to measure and where. Send a model number or site photo if you have one.



